Job Name: Location: Date:
Purchaser: Engineer:
Submitted to: For Reference Approval Construction
System Designation: Schedule No.:
Cooling*
Rated Capacity
...................................8,400 Btu/h
Minimum to Maximum Capacity Range
.........3,100 - 10,900 Btu/h
SEER
.........................................15.0 Btu/h/W
EER
..........................................12.0 Btu/h/W
Total Input
...........................................700 W
Heating at 47°F*
Rated Capacity
..................................10,900 Btu/h
Minimum to Maximum Capacity Range
.........3,100 - 14,100 Btu/h
HSPF
..........................................9.6 Btu/h/W
COP
.................................................3.44
Total Input
...........................................930 W
Heating at 17°F*
Rated Capacity
...................................6,200 Btu/h
Rated Total Input
.....................................740 W
COP
.................................................2.46
Maximum Capacity
................................8,300 Btu/h
Maximum Total Input
.................................1,040 W
* Rating Conditions (Cooling) - Indoor: 80ºF (27ºC) DB, 67ºF (19ºC) WB; Outdoor: 95ºF (35ºC) DB,
75ºF (24ºC) WB.
(Heating at 47ºF) - Indoor: 70ºF (21ºC) DB, 60ºF (16ºC) WB; Outdoor: 47ºF (8ºC) DB, 43ºF (6ºC) WB.
(Heating at 17ºF) - Indoor: 70ºF (21ºC) DB, 60ºF (16ºC) WB; Outdoor: 17ºF (-8ºC) DB, 15ºF (-9ºC) WB.
Electrical Requirements
Power Supply
....................... 208 / 230V, 1-Phase, 60 Hz
Recommended Fuse/Breaker Size
..........................15 A
Voltage
Indoor - Outdoor S1-S2
..........................AC 208 / 230V
Indoor - Outdoor S2-S3
............................ DC 12-24V
OPERATING CONDITIONS
Indoor Intake Air Temp. Outdoor Intake Air Temp.
Cooling
Maximum 95°F (35°C) DB, 71°F (22°C) WB 115°F (46°C) DB
Minimum 67°F (19°C) DB, 57°F (14°C) WB 14°F (-10°C) DB
Heating
Maximum 80°F (27°C) DB, 67°F (19°C) WB 75°F (24°C) DB, 65°F (18°C) WB
Minimum 70°F (21°C) DB, 60°F (16°C) WB -4°F (-20°C) DB, -5°F (-21°C) WB
Indoor Unit
MCA ...............................................1 A
Fan Motor Output ...................................15 W
Fan Motor .....................................0.23 F.L.A.
Airow (Lo - Med - Hi)................ 280 - 320 - 350 Dry CFM
250 - 290 - 320 Wet CFM
Air Filter .........................Polypropylene Honeycomb
Sound Pressure Level (Lo - Med - Hi) .........29 - 32 - 38 dB(A)
DIMENSIONS UNIT INCHES / MM GRILLE INCHES / MM
W 22-7/16 / 570 25-5/8 / 650
D 22-7/16 / 570 25-5/8 / 650
H 8-3/16 / 208 13/16 / 19
Weight (Unit/Grille)
Lbs............................................. 36 / 7
kg............................................. 16 / 3
External Finish (Unit/Grille) .......... Galvanized-steel Sheets /
Munsell 6.4Y 8.9 / 0.4
Field Drainpipe Size O.D.......................1-1/4" / 32 mm
Outdoor Unit
Compressor .............................DC Inverter-driven
MCA ..............................................12 A
MOCP.............................................15 A
Fan Motor .....................................0.50 F.L.A.
Sound Pressure Level
Cooling ......................................46 dB(A)
Heating ......................................50 dB(A)
DIMENSIONS INCHES / MM
W 31-1/2 / 800
D 11-1/4 / 285
H 21-5/8 / 550
Weight ....................................66 lbs. / 30 kg
External Finish ......................Munsell No. 3Y 7.8 / 1.1
Refrigerant Type ...................................R410A
Refrigerant Pipe Size O.D.
Gas Side .................................3/8" / 9.52 mm
Liquid Side................................1/4" / 6.35 mm
Max. Refrigerant Pipe Length...................... 65' / 19 m
Max. Refrigerant Pipe Height Difference ............. 40' / 12 m
Connection Method ................................Flared
SUBMITTAL DATA: SLZ-KA09NA & SUZ-KA09NA. . . . . . . . . . . . . . . . . . . .9,000 BTU/H CEILING-CASSETTE HEAT-PUMP SYSTEMS
Indoor Unit: SLZ-KA09NA
Outdoor Unit: SUZ-KA09NA
OPTIONAL ACCESSORIES
Indoor Unit
□ Grille (SLP-15AAUW; required - shipped with unit)
Outdoor Unit
□ Drain Pan Heater (MAC-640BH-U)
□ Drain Socket (MAC-860DS)
□ Three-pole Disconnect Switch (TAZ-MS303)
□ Air Outlet Guide (MAC-856SG)
□ Mounting Base (DSD-400N)
□ Mounting Pad (ULTRILITE1)
GENERAL FEATURES
• Four-way 2'x2' ceiling-cassette indoor unit for residential applications
• Built-in drain mechanism for condensate removal; lifts to 19-11/16"
• Setback down to 50°F when used with MRCH1 Central Controller
• Wide air-ow pattern for better air distribution
• Design features ventilation air intake knockout
• Long-life air lter included with indoor unit
• Indoor unit powered from outdoor unit using A-Control
• Automatic fan speed control; auto restart following a power outage
• Limited warranty: ve years on parts/defects, seven years on compressors
Controller Options
□ Wireless Remote Controller Kit (MHK1) with Wall-mounted Central
Controller (MRCH1), Wireless Receiver (MIFH1), and cable*
□ Wall-mounted Central Controller (MRCH1)*
□ Wireless Receiver (MIFH1)*
□ Portable Central Controller (MCCH1; for use with Wireless Remote
Controller Kit MHK1)*
□ Outdoor Air Sensor (MOS1; for use with Central Controller (MRCH1),
Wireless Remote Controller Kit (MHK1) and Portable Central
Controller (MCCH1)*
*See Submittal for information on each option.
□ Wall-mounted Wired Remote Controller (PAR-21MAA)
□ M-NET Control Adapter (MAC-399IF)
□ Remote Temperature Sensor (M21-JKO-307)
□ Handheld Wireless Remote Controller (PAR-FL32MA; req. PAR-SA9FA)
□ Receiver Kit for PAR-FL32MA Handheld Wireless Remote Controller
(PAR-SA9FA)
□ Lockdown Bracket for Handheld Controller (RCMKP1CB)