Job Name:
:etaD:ecnerefeR eludehcS
Manufactured for Mitsubishi Electric US, Inc.
Designed for PUHY-P-T/Y(S)KMU, and PURY-P-T/Y(S)KMU Series Units
GENERAL FEATURES
- Allows system to operate at 100% COOLING capacity at reduced outdoor temperatures
** PUHY Y-Series Outdoor Units -
Now down to -10
o
FDB Outdoor Temp.
** PURY R2-Series Outdoor Units -
Now down to -10
o
FDB Outdoor Temp.
IMPORTANT! The low ambient hood is only active when the outdoor unit is in cooling mode. On R2 (PURY) systems when the
outdoor unit is in heating mode, the hood is inactive. Indoor units that require cooling during this time, when the outdoor
temperature is below 21° F, will not function properly.
-
the low ambient hood.
- Hood constructed of 20 gauge, hot-dipped galvanized G-90 steel.
-
- Designed to work with both 208/230 and 460 3-phase units.
- NEMA 4X control box protects electrical components from the elements.
- ETL Recognized Component.
- Hood easily installs and connects to outdoor unit with plug in electrical connections.
-
or snow gaurds are easy to install with existing (wire guard) fasteners & provided screws.
NOTES:
** Hood and wind deflectors must be used together to achieve low operational range (for cooling operation systems only)
Outdoor unit must be mounted at least 18" off the ground or 12" above the highest average snow depth whichever is greater.
The outdoor unit may require additional mounting restraints depending on the mounting location. See installation instructions for guidelines.
4000292
Patent Pending
SPECIFICATIONS
Carton Dimensions
H x W x L.tW pihS.tW teNlacirtcelEnoitpircseDrebmuN traP
LAHK-1
Low Ambient Hood Assembly (master) with
damper control box
For single fan modules
208/230 1-phase
.20 amp
64 lbs.
(29 kg)
70 lbs.
(32 kg)
43" L x 36" W x 30-1/2" H
(1,092 x 914 x 775 mm)
LAHK-2
Low Ambient Hood Assembly (subordinate)
Combined with the LAHK-1 for double fan
(P120 and P144) modules
Controlled by
LAHK-1
56 lbs.
(25 kg)
62 lbs.
(28 kg)
43" L x 36" W x 30-1/2" H
(1,092 x 914 x 775 mm)