Air-Conditioners For Building ApplicationOUTDOOR UNITPURY-P-TJMU-A (-BS)PURY-P-YJMU-A (-BS)For use with R410AGBFEINSTALLATION MANUALFor safe and corre
10GBA (Unit: mm [in])OutdoormodelUnit combination A A1 *1 A2 *1unit 1 unit 2 High-pressure side Low-pressure side High-pressure side Low-pressure side
11GB10. Additional refrigerant chargeAt the time of shipping, the outdoor unit is charged with refrigerant.This charge does not include the amount nee
12GB<Example>Indoor 1: 30 A: ø28.58 mm [1-1/8 in] 40 m [131 ft] a: ø9.52 mm [3/8 in] 10 m [32 ft]At the conditionsbelow:2: 96 B: ø9.52 mm [3
13GB<Refrigerant piping connection examples>[Fig.10.2.2]<Front piping and bottom post-piping> (Sold separetely) (Unit: mm [in])No.123Shap
14GBSatisfy the minimum insertion depth in the table below when expanding on-site pipingPipe diameter (mm [in])Minimum insertion depth (mm [in])5 [7/3
15GBNote:Always add an appropriate amount of refrigerant. Also always charge •the system with liquid refrigerant.Use a gauge manifold, charging hose,
16GB11.1. Caution1 Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations and
17GB11.3. Wiring transmission cables1 Types of control cables1. Wiring transmission cablesTypes of transmission cables: Shielding wire CVVS, CPEVS or
18GB2 Wiring examplesController name, symbol and allowable number of controllers.•Name Code Possible unit connectionsOutdoor unit Main unit OC – (*2)S
19GB[Fig. 11.3.3] Combination of outdoor units and transmission booster unitMEICBCM1M2 STB5ICM1M2 STB5RPGroundABABABSTB2ABSTB3L15L18MEICM1M2 STB5ICM1M
2GB1.1. Before installation and electric workX Before installing the unit, make sure you read all the “Safety precautions”.X The “Safety precaution
20GB3 Transmission booster [Fig. 11.3.3]Max transmission cable length (M-NET cable): • 1 L11 + L12 + L13 + L14 + L16 + L17 200 m [656 ft] (1.25 mm2 [
21GB12. Test run/Typical unit operationThe events listed in the table below are normal occurrences and do not represent operation problems.Events Disp
WT05788X01HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPANPlease be sure to put the contact address/telephone number on
3GBInstall the power cable so that tension is not applied to the cable.•- Tension may cause the cable to break and generate heat and cause a fi re.Ins
4GB3. Combination of outdoor unitsComponent units of PURY-P168 to P288 are listed below.Outdoor unit model Component unit modelPURY-P72TJMU-A(-BS) -
5GB6. Space required for unit installation and operation1 In case of single installationSecure enough space around the unit as shown in the fi gure be
6GB2 In case of collective installation and continuous installation[Fig. 6.0.2]30450*300*CBBCA[11-13/16][17-23/32][1-3/16]100450* 100*BBCCA[3-15/16][1
7GB8.1. Installation[Fig. 8.1.1] 30mm[1-3/16 in]ABCAField-supplied M10 anchor boltBCorner is not seated.CFixing bracket for the hole-in anchor bolt (
8GB9. Refrigerant piping installationThe pipe is connected via a terminal-branch type connection in which refrigerant piping from the outdoor unit is
9GB9.2. Refrigerant piping system Connection example [Fig. 9.2.1][Outdoor model: P72 ~ P144]BAabcdABCEF EE[Outdoor model: P168~ P288]aCbBc dfDEAeA1un