Mitsubishi Electric PLA-A24BA4 Manuale Utente

Navigare online o scaricare Manuale Utente per Climatizzatori a split Mitsubishi Electric PLA-A24BA4. Job Name: Location: Date: Purchaser: Engineer: Submitted to: For Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 3
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 0
Job Name: Location: Date:
Purchaser: Engineer:
Submitted to: For Reference Approval Construction
Unit Designation: Schedule No.:
Indoor Unit: PLA-A30BA4
Outdoor Unit: PUZ-A30NHA4
OPERATING CONDITIONS
Indoor Intake Air Temp. Outdoor Intake Air Temp.
Cooling
Maximum 95ºF (35ºC) DB, 71ºF (22ºC) WB 115ºF (46ºC) DB
Minimum 67ºF (19ºC) DB, 57ºF (14ºC) WB 0ºF** (-18ºC) DB
Heating
Maximum 80ºF (27ºC) DB, 67ºF (19ºC) WB 70ºF (21ºC) DB, 59ºF (15ºC) WB
Minimum 70ºF (21ºC) DB, 60ºF (16ºC) WB 12ºF (-11ºC) DB, 10ºF (-12ºC) WB
** With optional wind bafe accessory installed. If not installed, the minimum
temperature will be 2F (-C) DB.
Indoor Unit
MCA .............................................. 1 A
Fan Motor ...................................0.51 F.L.A.
Fan Motor Output ...................................50 W
Airow (Lo - M1 - M2 - Hi) ....... 490 - 570 - 640 - 740 Dry CFM
460 - 530 - 600 - 710 Wet CFM
Sound Level (Lo - M1 - M2 - Hi) ..........28 - 30 - 32 - 34 dB(A)
SHF ............................................. 0.73
Moisture Removal................................ 7.2 pt./h
DIMENSIONS UNIT INCHES / MM PANEL INCHES / MM
W 33-1/16 / 840 37-3/8 / 950
D 33-1/16 / 840 37-3/8 / 950
H 10-3/16 / 258 1-3/8 / 35
Weight (Unit/Grille)
lbs. ............................................ 51 / 13
kg .............................................. 23 / 6
External Finish ....................Munsell No. 6.4Y 8.9 / 0.4
Field Drainpipe Size O.D......................1-1/4" / 32 mm
Outdoor Unit
Compressor ..................DC Inverter-driven Twin Rotary
MCA ............................................…25 A
MOCP............................................ 40 A
Fan Motor ....................................0.75 F.L.A.
Sound Pressure Level
Cooling .......................................48 dB(A)
Heating .......................................50 dB(A)
DIMENSIONS INCHES / MM
W 37-3/8 / 950
D 13 + 1-3/16 / 330 + 30
H 37-1/8 / 943
Weight ...................................165 lbs. / 75 kg
External Finish ......................Munsell No. 3Y 7.8 / 1.1
Refrigerant Type .................................. R410A
Refrigerant Pipe Size O.D.
Gas Side ................................5/8" / 15.88 mm
Liquid Side................................3/8" / 9.52 mm
Max. Refrigerant Pipe Length.....................165' / 50 m
Max. Refrigerant Pipe Height Difference ............100' / 30 m
Connection Method ................................Flared
SUBMITTAL DATA: PLA-A30BA4 & PUZ-A30NHA4. . . . . . . . . . . . . . . . .30,000 BTU/H CEILING CASSETTE HEAT PUMP SYSTEM
Cooling*
Rated Capacity...............................30,000 Btu/h
Minimum Capacity ............................12,000 Btu/h
SEER ......................................13.6 Btu/h/W
EER ....................................... 7.3 Btu/h/W
Total Input.......................................4,100 W
Heating at 47F*
Rated Capacity...............................32,000 Btu/h
Minimum Capacity ............................12,000 Btu/h
HSPF .......................................8.7 Btu/h/W
COP ............................................. 2.78
Total Input.......................................3,370 W
Heating at 17F*
Rated Capacity...............................23,000 Btu/h
Total Input.......................................3,050 W
COP ............................................. 2.20
* Rating Conditions (Cooling) - Indoor: 80ºF (27ºC) DB, 67ºF (19ºC) WB. Outdoor: 95ºF (3C) DB, 75ºF (24ºC) WB.
(Heating at 47ºF) - Indoor: 70ºF (21ºC) DB, 60ºF (16ºC) WB. Outdoor: 47ºF (8ºC) DB, 4F (6ºC) WB.
(Heating at 17ºF) - Indoor: 7F (21ºC) DB, 6F (16ºC) WB. Outdoor: 17ºF (-8.3ºC) DB, 15ºF (-9.4ºC) WB.
Electrical Requirements
Power Supply ....................208 / 230V, 1-Phase, 60 Hz
Recommended Fuse/Breaker Size.......................30 A
Voltage
Indoor - Outdoor S1-S2 ......................AC 208 / 230V
Indoor - Outdoor S2-S3 ............................DC 24V
GENERAL FEATURES
• Compact side-discharge outdoor unit
• Setback down to 50°F when used with MRCH1 Central Controller
• Quiet operation—indoor and outdoor units
• Built-in drain lift mechanism for condensate removal; lifts to 33-7/16"
• Wide air ow pattern for better air distribution
Auto wave airow in heating mode—unit independently cycles
through horizontal and vertical positions for more even heat distribution
• Independent vane adjustment
Automatic fan speed control
Limited warranty: ve years on parts/defects, seven years on compressors
OPTIONAL ACCESSORIES
Indoor Unit
□ i-see Sensor Corner Panel (PAC-SA1ME)
□ Multi-function Casement (PAC-SH53TM)
Air Outlet Shutter Plates (PAC-SH51SP)
□ High-efciency (MERV 10) Filter (PAC-SH59KF)
Outdoor Unit
□ Drain Pan (PAC-SG64DP)
□ Drain Socket (PAC-SG61DS)
Three-pole Disconnect Switch (TAZ-MS303)
□ Wind Bafe (WB-PA2)
Air Outlet Guide (PAC-SG59SG)
□ Mounting Base (DSD-400N)
□ Mounting Pad (ULTRILITE2)
□ Wall-mounting Brackets (CWMB1)
Controller Options
□ Wireless Remote Controller Kit (MHK1) with Wall-mounted Central
Controller (MRCH1), Wireless Receiver (MIFH1), and cable*
□ Wall-mounted Central Controller (MRCH1)*
□ Wireless Receiver (MIFH1)*
□ Portable Central Controller (MCCH1; for use with Wireless Remote
Controller Kit MHK1)*
□ Outdoor Air Sensor (MOS1; for use with Central Controller (MRCH1),
Wireless Remote Controller Kit (MHK1) and Portable Central
Controller (MCCH1)*
*See Submittal for information on each option.
□ Wall-mounted Wired Remote Controller (PAR-21MAA)
□ M-NET Adapter (PAC-SF81MA)
□ CN51 Connector for Multiple Remote Controller Adapters/Duct Fan
Controller (PAC-725AD)
□ CN24 Relay Kit (CN24RELAY-KIT-CM)
□ CN32 Connector for Remote On/Off (PAC-715AD)
□ Remote Temperature Sensor (PAC-SE41TS)
□ Remote Operation Adapter - Display and On/Off (PAC-SF40RM)
□ Handheld Wireless Remote Controller (PAR-FL32MA; req. PAR-SA9FA)
□ Wireless Signal Receiver Module (PAR-SA9FA)
□ Lockdown Bracket for Handheld Controller (RCMKP1CB)
□ Control/Service Tool (PAC-SK52ST)
Vedere la pagina 0
1 2 3

Sommario

Pagina 1 - Purchaser: Engineer:

Job Name: Location: Date:Purchaser: Engineer:Submitted to: For Reference Approval ConstructionUnit Designation: Schedule No.:

Pagina 2 - DIMENSIONS: PLA-A30BA4

DIMENSIONS: PLA-A30BA414-27/3211-3/162-3/8+50(7.5)+35-5(160)(500)(950)FloorMin.94-1/2(2400)from floorEntireperiphery(36)(83)(83)(36)(500)(950)(597)(59

Pagina 3 - DIMENSIONS: PUZ-A30NHA4

3400 Lawrenceville Suwanee RdSuwanee, GA 30024Tele: 678-376-2900 • Fax: 800-889-9904Toll Free: 800-433-4822 (#3)www.mehvac.comSpecications are subjec

Commenti su questo manuale

Nessun commento