Air-Conditioners For Building Application INDOOR UNITPKFY-P·VKM-EEnglishFor use with the R410A, R407C & R22
106. Electrical work6.1. Electrical work PKFY-P·VKM-E (Fig. 6-1)Connection can be made without removing the front panel.1. Open the front grille, rem
116.4. Connecting remote controller, indoor and outdoor transmission cables (Fig. 6-3)• Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized
Please be sure to put the contact address/telephone number on this manual before handing it to the customer.x Low Voltage Directive 2006/95 EECx Ele
2X Before installing the unit, make sure you read all the “Safety precautions”.X Please report to your supply authority or obtain their consent before
32. Installation location3. Installing the indoor unit3.1. Check the indoor unit accessories (Fig. 3-1)The indoor unit should be supplied with the f
43. Installing the indoor unit PKFY-P·VKM-EFig. 3-7Fig. 3-6AAFig. 3-8ABDCEFig. 3-10Fig. 3-93.2.3. Installing the wall mounting fixtureX Since the i
53. Installing the indoor unitFig. 3-11BACEDLeakage check of the L-shaped connection pipe connection portion1. Attach the charge nut 5 to the liquid
63.5. Mounting the indoor unit1. Affix the mount board 1 to the wall.2. Hang the indoor unit on the hook positioned on the upper part of the mount boa
74. Installing the refrigerant piping90°±0.5°øAR0.4~R0.8A45±2°BCDFig. 4-14.1. Connecting pipes (Fig. 4-1)• When commercially available copper pipes
84. Installing the refrigerant pipingFig. 4-4 PKFY-P·VKM-EBADC4.3. Refrigerant piping (Fig. 4-3)Indoor unit1. Remove the flare nut and cap of the in
9Fig. 5-15. Drainage piping work5.1. Drainage piping work (Fig. 5-1)• Drain pipes should have an inclination of 1/100 or more.• For extension of th