Job Name: Location: Date:
Purchaser: Engineer:
Submitted to: For Reference Approval Construction
Unit Designation: Schedule No.:
Cooling*
Rated Capacity...............................30,000 Btu/h
Minimum Capacity ............................12,000 Btu/h
SEER ......................................14.5 Btu/h/W
EER ....................................... 8.0 Btu/h/W
Total Input......................................3,760 W
Heating at 47°F*
Rated Capacity...............................32,000 Btu/h
Minimum Capacity ............................12,000 Btu/h
HSPF (IV) ....................................9.2 Btu/h/W
COP ............................................. 2.92
Total Input.......................................3,210 W
Heating at 17°F*
Rated Capacity...............................23,000 Btu/h
Total Input......................................2,940 W
COP ............................................. 2.29
* Rating Conditions (Cooling)-Indoor: 80ºF (27ºC) DB/67ºF (19ºC) WB. Outdoor: 95ºF (35ºC) DB/75ºF (24ºC) WB.
(Heating) - Indoor: 70ºF (21ºC) DB / 60ºF (16ºC) WB. Outdoor: 47ºF (8ºC) DB / 43ºF (6ºC) WB.
(Heating at 17ºF) - Indoor: 70ºF (21ºC) DB / 60ºF (16ºC) WB. Outdoor: 17ºF (-8ºC) DB / 15ºF (-9ºC) WB.
Electrical Requirements
Power Supply ....................208 / 230V, 1-Phase, 60 Hz
Recommended Fuse/Breaker Size.......................30 A
Voltage
Indoor - Outdoor S1-S2 ......................AC 208 / 230V
Indoor - Outdoor S2-S3 ............................DC 24V
Indoor Unit: PCA-A30KA4
Outdoor Unit: PUZ-A30NHA4
OPERATING CONDITIONS
Indoor Intake Air Temp. Outdoor Intake Air Temp.
Cooling
Maximum 95ºF (35ºC) DB, 71ºF (22ºC) WB 115ºF (46ºC) DB
Minimum 67ºF (19ºC) DB, 57ºF (14ºC) WB 0ºF** (-18ºC) DB
Heating
Maximum 80ºF (27ºC) DB, 67ºF (19ºC) WB 70ºF (21ºC) DB, 59ºF (15ºC) WB
Minimum 70ºF (21ºC) DB, 60ºF (16ºC) WB 12ºF (-11ºC) DB, 10ºF (-12ºC) WB
** With optional wind bafe accessory installed. If not installed, the minimum
temperature will be 23ºF (-5ºC) DB.
Indoor Unit
MCA .............................................. 1 A
Fan Motor ...................................0.54 F.L.A.
Fan Motor Output ...................................95 W
Airow (Lo - Mid1 - Mid2 - Hi)..... 565 - 600 - 635 - 705 Dry CFM
530 - 565 - 600 - 670 Wet CFM
Air Filter ........................ Polypropylene Honeycomb
Sound Pressure Level (Lo - Mid1 - Mid2 - Hi).........35 - 37 - 39 - 41 dB(A)
SHF ............................................. 0.69
Moisture Removal................................ 8.3 pt./h
DIMENSIONS UNIT INCHES / MM
W 50-3/8 / 1,280
D 26-3/4 / 680
H 9-1/16 / 230
Weight. ....................................71 lbs. / 32 kg
External Finish ....................Munsell No. 6.4Y 8.9 / 0.4
Field Drainpipe Size O.D.....................1-1/16" / 26 mm
Outdoor Unit
Compressor ..................DC Inverter-driven Twin Rotary
MCA ..............................................25 A
MOCP............................................ 40 A
Fan Motor ....................................0.75 F.L.A.
Sound Pressure Level
Cooling .................................... . .48 dB(A)
Heating ..................................... .50 dB(A)
DIMENSIONS INCHES / MM
W 37-3/8 / 950
D 13 + 1-3/16 / 330 + 30
H 37-1/8 / 943
Weight ...................................165 lbs. / 75 kg
External Finish ......................Munsell No. 3Y 7.8 / 1.1
Refrigerant Type .................................. R410A
Refrigerant Pipe Size O.D.
Gas Side ................................5/8" / 15.88 mm
Liquid Side................................3/8" / 9.52 mm
Max. Refrigerant Pipe Length.....................165' / 50 m
Max. Refrigerant Pipe Height Difference ............100' / 30 m
Connection Method ................................Flared
SUBMITTAL DATA: PCA-A30KA4 & PUZ-A30NHA4. . . . . . . . . . . . . . . . 30,000 BTU/H CEILING-SUSPENDED HEAT-PUMP SYSTEM
GENERAL FEATURES
• Ceiling-suspended indoor unit for residential and commercial applications
• Shiny white cabinet; compact design
• Standard air lter is included with indoor unit; high-efciency
lter is available as an option
• Setback down to 50°F when used with MRCH1 Central Controller
• Quiet operation—both indoor and outdoor units
• Self-check function—integrated diagnostics
• Limited warranty: ve years on parts/defects, seven years on compressors
OPTIONAL ACCESSORIES
Indoor Unit
□ Mini Condensate Pump (PAC-SH84DM, 230V)
□ High-efciency Filter (PAC-SH89KF)
i-see Sensor with Mount (PAC-SH91MK-E)
Outdoor Unit
□ Drain Pan (PAC-SG64DP)
□ Drain Socket (PAC-SG61DS)
Three-pole Disconnect Switch (TAZ-MS303)
□ Wind Bafe (WB-PA2)
Air Outlet Guide (PAC-SG59SG)
□ Mounting Base (DSD-400N)
□ Mounting Pad (ULTRILITE2)
□ Wall-mounting Brackets (CWMB1)
Controller Options
□ Wireless Remote Controller Kit (MHK1) with Wall-mounted Central
Controller (MRCH1), Wireless Receiver (MIFH1), and cable*
□ Wall-mounted Central Controller (MRCH1)*
□ Wireless Receiver (MIFH1)*
□ Portable Central Controller (MCCH1; for use with Wireless Remote
Controller Kit MHK1)*
□ Outdoor Air Sensor (MOS1; for use with Central Controller (MRCH1),
Wireless Remote Controller Kit (MHK1) and Portable Central
Controller (MCCH1)*
*See Submittal for information on each option.
□ Wall-mounted Wired Remote Controller (PAR-21MAA)
□ M-NET Adapter (PAC-SF81MA)
□ CN51 Connector for Multiple Remote Controller Adapters/Duct Fan
Controller (PAC-725AD)
□ CN32 Connector for Remote On/Off (PAC-715AD)
□ Remote Temperature Sensor (PAC-SE41TS)
□ Remote Operation Adapter - Display and On/Off (PAC-SF40RM)
□ Wireless Remote Controller Kit (PAR-SL93B)
□ i-See Sensor and Wireless Remote Controller Kit (PAR-SA92MW)
□ Lockdown Bracket for Handheld Controller (RCMKP1CB)
□ Control/Service Tool (PAC-SK52ST)
Vedere la pagina 0
1 2 3

Sommario

Pagina 1 - Purchaser: Engineer:

Job Name: Location: Date:Purchaser: Engineer:Submitted to: For Reference Approval ConstructionUnit Designation: Schedule No.:

Pagina 2 - DIMENSIONS: PCA-A30KA4

DIMENSIONS: PCA-A30KA4[]"ventilation air()[]"[FRONT VIEWLOOKING THROUGH THE UNIT][BACK VIEW]If the piping is installed in the backof the uni

Pagina 3 - DIMENSIONS: PUZ-A30NHA4

3400 Lawrenceville Suwanee RdSuwanee, GA 30024Tele: 678-376-2900 • Fax: 800-889-9904Toll Free: 800-433-4822 (#3)www.mehvac.comSpecications are subjec

Commenti su questo manuale