CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 4
3. SPECIFICATION ················································ 5
4. NOISE CRITERIA CURVES ······························ 6
5. OUTLINES AND DIMENSIONS ························ 8
6. WIRING DIAGRAM ············································ 9
7. REFRIGERANT SYSTEM DIAGRAM ············· 10
8. SERVICE FUNCTIONS ····································11
9. MICROPROCESSOR CONTROL ··················· 13
10. TROUBLESHOOTING ····································· 20
11. DISASSEMBLY INSTRUCTIONS ···················· 39
SPLIT-TYPE AIR CONDITIONERS
Outdoor unit service manual
MUZ-GE·VA Series (OBH516)
MXZ-A·VA Series (OB377)
MXZ-8A140A (OC316)
MXZ-B·VA Series (OB554)
SERVICE MANUAL
No. OBH515
REVISED EDITION-E
INDOOR UNIT
PARTS CATALOG (OBB515)
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
Models
MSZ-GE22VA -
E1
MSZ-GE25VA -
E1
MSZ-GE35VA -
E1
MSZ-GE42VA -
E1
MSZ-GE50VA -
E1
MSZ-GE60VA -
E1
MSZ-GE71VA -
E1
Revision E:
• Detail of the indoor fan speed control in COOL or
DRY operation has been added (9-1.3, 9-2.3).
Please void OBH515 REVISED EDITION-D.
MSZ-GE22VA
MSZ-GE25VA
MSZ-GE35VA
MSZ-GE42VA
MSZ-GE50VA
Vedere la pagina 0
1 2 3 4 5 6 ... 47 48

Sommario

Pagina 1 - INDOOR UNIT

CONTENTS1. TECHNICAL CHANGES ··································· 32. PART NAMES AND FUNCTIONS ····················· 43. SPECIFICATION ················

Pagina 2 - Revision E:

10IndoorheatexchangerFlared connectionRoom temperaturethermistorRT11Flared connectionRefrigerant pipe ø9.52 (MSZ-GE22/25/35/42VA)

Pagina 3 - TECHNICAL CHANGES

118-1. TIMER SHORT MODEFor service, set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board.The time will be sh

Pagina 4 - PART NAMES AND FUNCTIONS

128-3. AUTO RESTART FUNCTIONWhen the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed

Pagina 5 - SPECIFICATION

13WIRELESS REMOTE CONTROLLERON TIMER buttonCLOCK SET buttonTIME SET buttonsFORWARD buttonBACKWARD buttonOFF TIMER buttonRESET buttoni save buttonVANE

Pagina 6 - NOISE CRITERIA CURVES

149-1. COOL ( ) OPERATION(1) Press OPERATE/STOP (ON/OFF) button.OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.(2) Select COOL

Pagina 7 - MSZ-GE60VA MSZ-GE71VA

159-4. AUTO CHANGE OVER ··· AUTO MODE OPERATIONOnce desired temperature is set, unit operation is switched automatically between COOL and HEAT operati

Pagina 8 - OUTLINES AND DIMENSIONS

16(7) SWING ( or ) modeBy selecting SWING mode with VANE CONTROL button, the horizontal vane swings vertically. (8) Cold air prevention in HEAT oper

Pagina 9 - WIRING DIAGRAM

17(4) SWING ( ) MODE By selecting SWING mode with WIDE VANE CONTROL button, the vertical vane swings horizontally. The remote controller displays “ ”

Pagina 10 - REFRIGERANT SYSTEM DIAGRAM

189-7. WEEKLY TIMER OPERATION (MSZ-GE60VA MSZ-GE71VA)• A maximum of 4 ON or OFF timers can be set for individual days of the week.• A maximum of 28 O

Pagina 11 - SERVICE FUNCTIONS

19(5) Press button to turn the weekly timer ON. ( lights.)•When the weekly timer is ON, the day of the week whose timer setting is complete, will

Pagina 12

2Revision A:• 11. DISASSEMBLY INSTRUCTIONS has been corrected.11-6. Photo 9 has been changed.Revision B:• MSZ-GE42VA - E1 and MSZ-GE50VA - E1 have bee

Pagina 13 - MICROPROCESSOR CONTROL

2010-1. CAUTIONS ON TROUBLESHOOTING1. Before troubleshooting, check the following1) Check the power supply voltage.2) Check the indoor/outdoor connect

Pagina 14 - INDOOR UNIT DISPLAY SECTION

211Lock25. How to install the horizontal vaneIf horizontal vane is not installed correctly, all of the operation indicator lamps will blink.In this ca

Pagina 15 - 1 2 3 4 5

2210-2. FAILURE MODE RECALL FUNCTIONOutline of the functionThis air conditioner can memorize the abnormal condition which has occurred once.Even thoug

Pagina 16 - Fan speed : Faster

232. Indoor unit failure mode tableUpper lamp of OP-ERATION INDICA-TOR lampAbnormal point (Failure mode) Condition Correspondence Not lighted Normal

Pagina 17 - PROGRAM TIMER

2410-3. INSTRUCTION OF TROUBLESHOOTINGIndoor unit oper-ates.Outdoor unit does not operate.If blinking of OPERATION INDI-CATOR lamp cannot be checked,

Pagina 18

2510-4. TROUBLESHOOTING CHECK TABLEBefore taking measures, make sure that the symptom reappears for accurate troubleshooting.When the indoor unit has

Pagina 19 - (E.O. SW)

26OPERATION INDICATORNo. Abnormal pointOperation indicator lamp Symptom Condition Correspondence1Attachment of the hori-zontal vaneAll lamps fl ash at

Pagina 20 - TROUBLESHOOTING

27 A Check of indoor fan motor10-6. TROUBLESHOOTING FLOWThe indoor fan motor error has occurred, and the indoor fan does not operate.Turn OFF the po

Pagina 21

28The indoor fan motor error has occurred, and the indoor fan does not operate.Turn OFF the power supply.Is there any foreign matter that interferes t

Pagina 22

29 B Check of remote controller and indoor electronic control P.C. board Check if the remote controller is exclusive for this air conditioner.Does th

Pagina 23

3MSZ-GE22VA - E1MSZ-GE25VA - E1MSZ-GE35VA - E1MSZ-GE42VA - E1MSZ-GE50VA - E1MSZ-GE60VA - E1MSZ-GE71VA - E1 1. New modelTECHNICAL CHANGES1

Pagina 24

30 C Check of indoor P.C. board and indoor fan motorTurn OFF the power supply.Remove indoor fan motor connector CN211 from indoor power P.C. board a

Pagina 25

31CN211R111Indoor electroniccontrol P.C.BoardIndoor terminalP.C. boardFuse(F11)Varistor(NR11)YesNo 1. The fan motor connector's lead wire is

Pagina 26 - MSZ-GE60VA MSZ-GE71VA

32 D How to check miswiring and serial signal errorMSZ-GE22VA MSZ-GE25VA MSZ-GE35VA MSZ-GE42VA MSZ-GE50VATurn OFF inverter-controlled lighting eq

Pagina 27 - A Check of indoor fan motor

33MSZ-GE60VA MSZ-GE71VATurn OFF inverter-controlled lighting equipment.Turn OFF the power supply and then turn ON again.Press EMERGENCY OPERATION swi

Pagina 28

34 E Check of installation of the horizontal vaneIs the stopper of the horizontal vane locked to the indoor unit correctly?YesNoRe-lock the stopper o

Pagina 29

35 F Electromagnetic noise enters into TV sets or radiosYesIs the unit earthed?NoEarth the unit.YesIs the distance between the antennas and the indoo

Pagina 30

361. Indoor power P.C. board, Indoor terminal P.C. boardMSZ-GE22VA MSZ-GE25VA MSZ-GE35VA10-7. TEST POINT DIAGRAM AND VOLTAGEIndoor terminal P.C. boa

Pagina 31

37Room temperature thermistor (RT11)Indoor coil thermistor (RT12, RT13)Temperature (°C)Resistance (kΩ)Timer short mode point JPG JPS (Refer to 8-1.)Ro

Pagina 32

38JR24JRREJRDFTJR07JRPRHJR19JRTUJR01Indoor terminal P.C. board Indoor electronic control P.C. boardPower monitor receiver SW P.C. boardFuse (F11)( )Va

Pagina 33

3911-1. MSZ-GE22VA MSZ-GE25VA MSZ-GE35VA MSZ-GE42VA MSZ-GE50VANOTE: Turn OFF power supply before disassembling.OPERATING PROCEDURE PHOTOS1. Removi

Pagina 34

4ACCESSORIESRemote controllerOperation indicator lampRemote control receiving sectionEmergency operation switch (E.O. SW) Horizontal vaneVertical vane

Pagina 35

40OPERATING PROCEDURE PHOTOS2. Removing the indoor electronic control P.C. board and the room temperature thermistor(1) Remove the panel (Refer to 1.)

Pagina 36 - MSZ-GE42VA MSZ-GE50VA

41OPERATING PROCEDURE PHOTOS4. Removing the nozzle assembly(1) Remove the panel (Refer to 1.) and the corner box.(2) Remove the indoor/outdoor connect

Pagina 37 - Resistance (kΩ)

42OPERATING PROCEDURE PHOTOS6. Removing the indoor fan motor, the indoor coil thermistor, and the line flow fan(1) Remove the panel (Refer to 1.) and

Pagina 38

4311-2. MSZ-GE60VA MSZ-GE71VANOTE: Turn OFF power supply before disassembling.OPERATING PROCEDURE PHOTOS1. Removing the panel(1) Remove the horizonta

Pagina 39 - Locking lever

44OPERATING PROCEDURE PHOTOS2. Removing the indoor electronic control P.C. board, the power monitor receiver SW P.C. board and the indoor terminal P.C

Pagina 40 - OPERATING PROCEDURE PHOTOS

45OPERATING PROCEDURE PHOTOS4. Removing the nozzle assembly(1) Remove the panel (Refer to 1.) and the corner box.(2) Remove the V.A. clamp, and then t

Pagina 41

46OPERATING PROCEDURE PHOTOS7. Removing the water cut, the indoor fan motor, the indoor coil thermistor, and the line flow fan(1) Remove the panel (Re

Pagina 43 - 11-2. MSZ-GE60VA MSZ-GE71VA

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN© Copyright 2008 MITSUBISHI ELECTRIC CO., LTDDistributed in Jun. 2010. N

Pagina 44

5Indoor modelMSZ-GE22VAMSZ-GE25VAMSZ-GE35VAMSZ-GE42VAMSZ-GE50VAMSZ-GE60VAMSZ-GE71VAPower supply Single phase 230 V, 50 HzElectrical dataPower input 1

Pagina 45

6MSZ-GE22VA MSZ-GE25VA90807060504030201063 125 250 500 1000 2000 4000 8000NC-60NC-50NC-40NC-30NC-20NC-70OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.000

Pagina 46

7MSZ-GE60VA MSZ-GE71VA Test conditionsCooling: Dry-bulb temperature 27°CWet-bulb temperature 19°CHeating: Dry-bulb temperature 20°CINDOOR UNITWALLMICR

Pagina 47

8Unit: mmMSZ-GE22VA MSZ-GE25VA MSZ-GE35VA MSZ-GE42VA MSZ-GE50VA211.5231.525321.5155 1558080225 2253191595852325669798785 6.51306195029550425643428

Pagina 48

9MSZ-GE22VA MSZ-GE25VA MSZ-GE35VAWIRING DIAGRAM6MSZ-GE42VA MSZ-GE50VAMSZ-GE60VA MSZ-GE71VA