Job Name: Location: Date:
Purchaser: Engineer:
Submitted to: For Reference Approval Construction
Unit Designation: Schedule No.:
Indoor Unit: MSZ-D30NA
Outdoor Unit: MUZ-D30NA
Indoor Unit
MCA ............................................... 1 A
Fan Motor ....................................0.76 F.L.A.
Airow
Cooling (Lo - Med - Hi) ..............389 - 639 - 848 Dry CFM
350 - 576 - 763 Wet CFM
Heating (Lo - Med - Hi) ..............445 - 639 - 848 Dry CFM
Sound Pressure Level
Cooling (Lo - Med - Hi) ....................32 - 42 - 49 dB(A)
Heating (Lo - Med - Hi)....................34 - 42 - 49 dB(A)
DIMENSIONS UNIT INCHES / MM
W 46-1/16 / 1,170
D 11-5/8 / 295
H 14-3/8 / 365
Weight ....................................40 lbs. / 18 kg
External Finish ....................Munsell No. 1.0Y 9.2 / 0.2
Field Drainpipe Size O.D......................5/8" / 15.88 mm
Remote Controller ................................Wireless
(Optional Wired Remote Controller PAR-21MAA
see Data Submittal Sheet)
Outdoor Unit
Compressor ................ . . . . . . DC Inverter-driven Rotary
MCA .............................................. 21 A
Fan Motor .....................................0.93 F.L.A.
Sound Pressure Level
Cooling ........................................55 dB(A)
Heating ........................................57 dB(A)
DIMENSIONS INCHES / MM
W 33-1/16 / 840
D 13 / 330
H 33-7/16 / 849
Weight ...................................141 lbs. / 64 kg
External Finish .......................Munsell No. 3Y 7.8 / 1.1
Refrigerant Type ................................... R410A
Refrigerant Pipe Size O.D.
Gas Side ................................5/8" / 15.88 mm
Liquid Side................................3/8" / 9.53 mm
Max. Refrigerant Pipe Length.....................100' / 30 m
Max. Refrigerant Pipe Height Difference .............50' / 15 m
Connection Method .................................Flared
SUBMITTAL DATA: MSZ-D30NA & MUZ-D30NA 30,000 BTU/H WALL-MOUNTED HEAT-PUMP SYSTEM
Wireless Remote Controller
OPTIONAL ACCESSORIES
Outdoor Unit
• Drain Socket Assembly (MAC-811DS)
Indoor Unit
• Three-pole Disconnect Switch (TAZ-MS303)
• M-NET Control Adapter (MAC-399IF)
• MA Contact Terminal Interface (MAC-397IF)
• Wired Remote Controller (PAR-21MAA; Requires MAC-3971)
• Centralized On/Off Remote Controller (MAC-821SC; Up to
eight units, requires one MAC-397IF per indoor unit)
• Condensate Pump (230V; SI3100-230)
Anti-allergy Enzyme Filter (Two pieces per set; MAC-1415FT)
GENERAL FEATURES
• Catechin and anti-allergy enzyme lters for high air-purication
capabilites
• Updated sleek, compact indoor unit design
• Remote-controlled wide airow enables ideal horizontal air
distribution
• Self-check function—onboard diagnostics
Advanced microprocessor control
Auto restart following a power outage
• Wireless remote controller
• Limited warranty: ve years on parts and defects and seven
years on compressors
Cooling*
Rated Capacity...............................30,700 Btu/h
Minimum Capacity .............................9,800 Btu/h
SEER ......................................14.5 Btu/h/W
Total Input......................................3,850 W
Heating at 47° F*
Rated Capacity...............................32,600 Btu/h
Minimum Capacity .............................8,700 Btu/h
HSPF .......................................8.2 Btu/h/W
Total Input......................................3,360 W
Heating at 17° F*
Rated Capacity...............................19,500 Btu/h
Rated Total Input ................................2,400 W
Maximum Capacity............................20,800 Btu/h
Maximum Total Input .............................2,620 W
* Rating Conditions (Cooling) - Indoor: 80ºF (27ºC) DB, 67ºF (19ºC) WB; Outdoor: 95ºF (35ºC)
DB, 75ºF (2C) WB.
(Heating at 47° F) - Indoor: 70ºF (21ºC) DB, 60ºF (16ºC) WB; Outdoor: 47ºF (8ºC) DB, 43ºF (6ºC) WB.
(Heating at 17° F) - Indoor: 70ºF (21ºC) DB, 60ºF (16ºC) WB; Outdoor: 17ºF (-8ºC) DB, 15ºF (-9ºC) WB.
Power Supply ....................208 / 230V, 1-Phase, 60 Hz
Breaker Size........................................25 A
Voltage
Indoor - Outdoor S1-S2 ......................AC 208 / 230V
Indoor - Outdoor S2-S3 .........................DC 12-24V
Indoor - Remote Controller.........................Wireless
OPERATING RANGE
Indoor Intake Air Temp. Outdoor Intake Air Temp.
Cooling
Maximum 90ºF (32ºC) DB, 73ºF (23ºC) WB 115ºF (46ºC) DB
Minimum 67ºF (19ºC) DB, 57ºF (14ºC) WB 14ºF (-10ºC) DB
Heating
Maximum 80ºF (27ºC) DB, 67ºF (19ºC) WB 75ºF (24ºC) DB, 65ºF (18ºC) WB
Minimum 70ºF (27ºC) DB, 60ºF (16ºC) WB 14ºF (-10ºC) DB, 13ºF (-11ºC) WB
Vedere la pagina 0
1 2

Sommario

Pagina 1 - Purchaser: Engineer:

Job Name: Location: Date:Purchaser: Engineer:Submitted to: For Reference Approval ConstructionUnit Designation: Schedule No.:

Pagina 2 - MUZ-D30NA

3400 Lawrenceville Suwanee RdSuwanee, GA 30024Tele: 678-376-2900 • Fax: 800-889-9904Toll Free: 800-433-4822 (#3)www.mehvac.comSpecications are subjec