VECTOR INVERTER INSTRUCTION MANUALFR-V5NE VECTOR INVERTER-INSTRUCTION MANUAL-IB-0600108E-A (0208) MEEVECTOR INVERTERPrinted in Japan Specifications su
2PRE-OPERATION INSTRUCTIONS1.3 StructureName Function1) RJ-45 modular jackConnect the 10BASE-T cable for Ethernet communication to make communication
32.INSTALLATION2.1 Pre-Installation InstructionsMake sure that the input power of the inverter is off.2.2 Installation (1) Remove the inverter front c
4INSTALLATIONWhen installing the inverter front cover, the cables to the inverter's control circuit terminals and option terminals should be rout
5INSTALLATION2.3 Removal(1) How to remove the control circuit terminal block Loosen the two mounting screws in both ends of the control circuit termin
63. OPERATION OVERVIEWBy fitting the Ethernet communication option (FR-V5NE) to the FR-V500 series inverter, you can performparameter setting, monitor
7OPERATION OVERVIEW3.2 Cable SpecificationConnect the option unit (FR-V5NE) to the Ethernet using the LAN cable indicated below.Cable used: Use cable
8OPERATION OVERVIEW3.4 General ProcedureStartGet the IP address (sub-network mask, gateway address as necessary) for the inverter from the network man
94. INVERTER SETTING4.1 Communication Parameter ListFitting the FR-V5NE to the inverter enables the following parameters to be set. Use the PU (FR-DU0
10INVERTER SETTING4.1.1 Parameters(1) Pr. 434 to Pr. 437 (IP address)Set the IP address of the FR-V5NE. (Set the IP address that was assigned by the s
11INVERTER SETTING4.2 Inverter Operation ModeChange the operation mode to the network operation mode to write, initialize, or reset parameters with th
A-1Thank you for choosing the Mitsubishi inverter option unit.This instruction manual gives handling information and precautions for use of this equi
125. FUNCTION OVERVIEWYou can perform the following functions efficiently using the Web browser of the personal computer.Parameter setting functionAll
13FUNCTION OVERVIEW5.1 Software Specifications5.1.1 Software configurationIn Ethernet communication, the software consists of the applet program, serv
146. SOFTWARE START AND SCREEN DESCRIPTION6.1 Software StartStart the Ethernet software by specifying the IP address of the FR-V5NE that was set in th
15SOFTWARE START AND SCREEN DESCRIPTION6.2 Main ScreenWhen you login, the following screen appears.CAUTIONNormally it takes 2 to 3 mins to start the s
16SOFTWARE START AND SCREEN DESCRIPTION6.2.1 Functions6.2.2 Parameter setting6.2.3 Parameter No and range6.2.4 Parameter setting buttonRefer to page 1
177. PARAMETER SETTINGSet the parameters.Refer to the inverter manual for details of the parameters.After changing any parameter value(s), click 8) [B
18PARAMETER SETTING7.1 Parameter Setting on All List Format PageDisplay all parameters of the inverter being connected.(1) Click the Updated Val field
19PARAMETER SETTING7.2 Parameter Setting on Functional List Format PageThis page displays specific parameters on a function-by-function basis from amo
20PARAMETER SETTING!Function button outlineMotor Used to display the parameter list related to motor setting.S Settings Used to display the parameter
21PARAMETER SETTING7.3 Parameter Setting on Individual List Format PageThis page can be used to list thefrequently used parameters or necessary parame
A-22. Injury Prevention3. Additional instructionsAlso note the following points to prevent an accidental failure, injury, electric shock, etc.:(1) Tra
22PARAMETER SETTING(2) Save in the Individual ListSave parameter No. currently displayed in the individual list in the file.Click [Save format] to sav
23PARAMETER SETTING7.4 Parameter Setting on Basic Settings PageYou can set the operation specifications roughly without a need to know the specific pa
24PARAMETER SETTING(2) Clicking [Confirmed] sets the parameters automatically and displays the parameter list.Click [Pre. page] to return to the prev
25PARAMETER SETTING7.5 DA1/DA2 CalibrationPressing [Click] in the Change Value field of Pr. 900 or Pr. 901 on the parameter setting page displays thef
26PARAMETER SETTING7.6 Bias/Gain of Speed Setting Voltage (Current)Pressing [Click] in the Change Value field of any of Pr. 902 to Pr. 905 and Pr. 917
27PARAMETER SETTING(2) Calibration with application of voltageChoosing the adjusting method "With the voltage source" (1)) monitors the Pres
28PARAMETER SETTING(3) Calibration at any point without application of voltageChoose the adjusting method "Any points without voltage source"
298. PARAMETER FUNCTION BUTTONS8.1 Change ListClicking [Change List] displays the following screen.The parameters whose values have been changed from
30PARAMETER FUNCTION BUTTONS8.2 Parameter InitializationClicking [Pr Init] initializes the parameters.The parameters can be initialized by "Param
31PARAMETER FUNCTION BUTTONS8.3 Block Read/Block WriteClicking [Blk Read] or [Blk Write] reads or writes data and displays the progress.CAUTION•••• Cl
A-3(3) Usage(4) Maintenance, inspection and parts replacement(5) Disposal(6) General instruction!Do not modify the equipment.!When parameter clear or
32PARAMETER FUNCTION BUTTONS8.4 SaveUsed to save parameter No., parameter setting (in the present setting column), and unit in the parameterlist. Save
33PARAMETER FUNCTION BUTTONS8.5 Upload and Change Value DisplayUsed to read the parameter list file saved and display on the change value field. Uploa
349. MONITORING9.1 Monitor ListThe following items can be monitored on the data display, meter display, oscilloscope and VFD statusscreens.(#...Can
35MONITORING9.2 Data DisplayUp to four different signals are displayed as numerical values in real time.The input and output states of the control te
36MONITORINGNo. Name Description1)Monitor function switchoverUsed to switch between the monitor functions (data display, meter display, oscilloscope,
37MONITORING9.3 Meter DisplayUp to four different signals are displayed as meters at regular time intervals.1)4)5)2)3))
38MONITORINGNo. Name Description1) Display item Select the item to be monitored.2) Meter displayThe monitor value is displayed as a meter (current val
39MONITORING9.4 OscilloscopeUp to four different signals, which have been received from the inverter in advance, are displayed on thepersonal compute
40MONITORINGNo. Name Description1)Sampling itemSelect the item to be sampled.<Sampling item>Refer to the Monitor List (Refer to page 34.)2)Sampl
41MONITORING(1) The following status panel appears at start of sampling.
CONTENTS1.PRE-OPERATION INSTRUCTIONS 11.1 Unpacking and Product Confirmation ...
42MONITORING(2) Clicking [Play Back] after sampling displays the following screen.*The full scale value of the speed is the Pr. 55 setting. Change the
43MONITORING9.5 Alarm HistoryPast eight alarms history can be displayed.No. Name Description1)Alarm HistoryUsed to display past eight alarms. Display
4410. DIAGNOSTICSThe output current, output voltage and other data are monitored at fixed intervals.10.1 VFD StatusNo. Name Description1) Monitor Valu
45DIAGNOSTICS10.2 DiagnosticsVarious status at inverter error occurrences can be displayed.No. Name Description1) Alarm HistoryShows the latest alarm
4611. MAIL SETTINGAt the occurrence of an inverter alarm, its definition is sent to the preset mail address.Mail is sent when the protective function
4712.ERROR CODES12.1 Error Code ListsWhen an error occurs, following error codes are displayed in the Information column 4) in the screen onpage 15).(
48 APPENDIXInverter Operation Mode(1)Operation mode switching conditionsBefore switching the operation mode, check that:1) The inverter is at a stop;2
49APPENDIX(2)Operation mode switching method*1 In the switch-over mode (Pr. 79 = 6), switching in E and F is allowed.Symbol Switching Type Switching M
50APPENDIX(3) Pr. 340 "link startup mode selection"You can select the operation mode at power-on or automatic restart after instantaneous po
51APPENDIX1(2)*0 PU or network operation Network operation mode (Switchover using software is not needed.)1 PU operation PU operation mode2 Network op
6.1 Software Start ...
52APPENDIX(4) Pr. 338 "operation command source", Pr. 339 "speed command source"In the network operation mode, commands from the e
53APPENDIXSelective functionsPr. 180 to Pr. 183, Pr. 187 settings *10Low-speed operation command, Remote setting (setting clear) (RL)— External — Exte
54APPENDIXExternal : Control by signal from external terminal is only valid.NET : Control from network is only valid.Combined : Control from both exte
55APPENDIX(5) Inverter ResetWhich resetting method is allowed or not allowed in each operation mode is described below.Resetting MethodOperation ModeN
MEMO
REVISIONS*The manual number is given on the bottom left of the back cover.Print Date *Manual Number RevisionAugust, 2002 IB(NA)-0600108E-A First editi
10. DIAGNOSTICS 4410.1 VFD Status...
MEMO
11.PRE-OPERATION INSTRUCTIONS1.1 Unpacking and Product ConfirmationTake the option unit out of the package, check the unit name, and confirm that the